Versión en texto ¿Qué es?Dateas es un sitio independiente no afiliado a entidades gubernamentales. La fuente de los documentos PDF aquí publicados es la entidad gubernamental indicada en cada uno de ellos. Las versiones en texto son transcripciones no oficiales que realizamos para facilitar el acceso y la búsqueda de información, pero pueden contener errores o no estar completas.
Fuente: Federal Register
Federal Register / Vol. 86, No. 151 / Tuesday, August 10, 2021 / Notices part 431, subpart R, appendix C
Appendix C, except that the liquid inlet saturation temperature test condition and liquid inlet subcooling temperature test condition shall be modified to 38 F and 5 F, respectively,
for both walk-in refrigerator unit coolers and walk-in freezer unit coolers, as detailed below. All other requirements of Appendix C and DOEs regulations remain applicable.
43641
In Appendix C, under section 3.1.
General modifications: Test Conditions and Tolerances, revise section 3.1.5., to read as follows:
3.1.5. Tables 15 and 16 shall be modified to read as follows:
TABLE 15-REFRIGERATOR UNIT COOLER
Unit Unit cooler cooler air air entering Liquid entering relative Saturated inlet Liquid inlet Test dry-bulb, humidity, suction saturation subcooling Compressor OF
%
temp, F temp, F temp, F
capacity description Test ob.iective
Off Cycle Fan Power
35
<50
-
-
Refrigeration Capacity Suction A
35
<50
25
38
Compressor Measure fan Off input power during compressor off cycle.
-
5
Compressor Determine Net On Refrigeration Capacity of Unit Cooler.
VerDate Sep<11>2014
17:05 Aug 09, 2021
Jkt 253001
PO 00000
Frm 00018
Fmt 4703
Sfmt 4725
E:FRFM10AUN1.SGM
10AUN1
EN10AU21.013
jbell on DSKJLSW7X2PROD with NOTICES
Note: Superheat to be set according to equipment specification in equipment or installation manual. If no superheat specification is given, a default superheat value of 6.5 F shall be used.
The superheat setting used in the test shall be reported as part of the standard rating.