Versione di testo Cosa è?Dateas è un sito indipendente non affiliato a entità governative. La fonte dei documenti PDF che pubblichiamo qui è l'entità governativa indicata in ciascuno di essi. Le versioni in testo sono trascrizioni che realizziamo per facilitare l'accesso e la ricerca di informazioni, ma possono contenere errori o non essere complete.

Source: Federal Register

Federal Register / Vol. 86, No. 86 / Thursday, May 6, 2021 / Rules and Regulations
24473

REFRIGERANTSSUBSTITUTES ACCEPTABLE SUBJECT TO USE CONDITIONSContinued End-use
Substitute
khammond on DSKJM1Z7X2PROD with RULES2

Residential and light commercial air conditioning and heat pumps new only, excluding self-contained room air conditioners.

VerDate Sep<11>2014

Decision
R32

18:29 May 05, 2021

Use conditions
Acceptable Subject to Use Conditions.

Jkt 253001

PO 00000

Further information
f For non-fixed equipment, including portable air conditioners, window air conditioners, packaged terminal air conditioners and packaged terminal heat pumps, on the outside of the product:
WARNINGRisk of Fire or ExplosionStore in a well ventilated room without continuously operating flames or other potential ignition.
g For fixed equipment, including rooftop units and split air conditioners, WARNINGRisk of Fire Auxiliary devices which may be ignition sources shall not be installed in the ductwork, other than auxiliary devices listed for use with the specific appliance. See instructions.
h All of these markings must be in letters no less than 6.4 mm 14 inch high.
The equipment must have red Pantone Matching System PMS 185 or RAL 3020 marked service ports, pipes, hoses, or other devices through which the refrigerant passes, to indicate the use of a flammable refrigerant.
This color must be applied at all service ports and other parts of the system where service puncturing or other actions creating an opening from the refrigerant circuit to the atmosphere might be expected and must extend a minimum of one 1 inch 25mm in both directions from such locations and shall be replaced if removed.
These refrigerants may be used only in new equipment specifically designed and clearly identified for the refrigerants i.e., none of these substitutes may be used as a conversion or retrofit refrigerant for existing equipment designed for other refrigerants.
These substitutes may only be used in air conditioning equipment that meets all requirements in the 3rd edition of UL 60335240.1 2 3 In cases where this appendix includes requirements more stringent than those of UL 60335240, the appliance must meet the requirements of this appendix in place of the requirements in the UL Standard.
The charge size for the equipment must not exceed the maximum refrigerant mass determined according to UL
60335240 for the room size where the air conditioner is used.
The following markings must be attached at the locations provided and must be permanent:
a On the outside of the air conditioning equipment:
WARNINGRisk of Fire. Flammable Refrigerant Used. To Be Repaired Only By Trained Service Personnel. Do Not Puncture Refrigerant Tubing.
b On the outside of the air conditioning equipment:
WARNINGRisk of Fire. Dispose of Properly In Accordance With Federal Or Local Regulations.
Flammable Refrigerant Used.
c On the inside of the air conditioning equipment near the compressor: WARNINGRisk of Fire.
Flammable Refrigerant Used. Consult Repair Manual/Owners Guide Before Attempting To Service This Product. All Safety Precautions Must be Followed.
d For any equipment pre-charged at the factory, on the equipment packaging: WARNINGRisk of Fire due to Flammable Refrigerant Used. Follow Handling Instructions Carefully in Compliance with National Regulations e On the indoor unit near the nameplate:
a. At the top of the marking: Minimum Installation height, X m W ft. This marking is only required if required by UL 60335240. The terms X and W shall be replaced by the numeric height as calculated per the UL
Standard. Note that the formatting here is slightly different than the UL Standard; specifically, the height in Inch-Pound units is placed in parentheses and the word and has been replaced by the opening parenthesis.
b. Immediately below a above or at the top of the marking if a is not required: Minimum room area operating or storage, Y m2 Z
ft2. The terms Y and Z shall be replaced by the numeric area as calculated per the UL
Standard. Note that the formatting here is slightly different than the UL Standard; specifically, the area in Inch-Pound units is placed in parentheses and the word and has been replaced by the opening parenthesis.
f For fixed equipment, including rooftop units and split air conditioners, WARNINGRisk of Fire Auxiliary devices which may be ignition sources shall not be installed in the ductwork, other than auxiliary devices listed for use with the specific appliance. See instructions.
g All of these markings must be in letters no less than 6.4 mm 14 inch high.

Frm 00031

Fmt 4701

Sfmt 4700

Applicable OSHA requirements at 29 CFR part 1910
must be followed, including those at 29 CFR 1910.94
ventilation and 1910.106 flammable and combustible liquids, 1910.110 storage and handling of liquefied petroleum gases, and 1910.1000 toxic and hazardous substances.
Proper ventilation should be maintained at all times during the manufacture and storage of equipment containing flammable refrigerants through adherence to good manufacturing practices as per 29 CFR
1910.106. If refrigerant levels in the air surrounding the equipment rise above one-fourth of the lower flammability limit, the space should be evacuated and reentry should occur only after the space has been properly ventilated.
Technicians and equipment manufacturers should wear appropriate personal protective equipment, including chemical goggles and protective gloves, when handling flammable refrigerants. Special care should be taken to avoid contact with the skin which, like many refrigerants, can cause freeze burns on the skin.
A class B dry powder type fire extinguisher should be kept nearby.
Technicians should only use spark-proof tools when working on air conditioning equipment with flammable refrigerants.
Any recovery equipment used should be designed for flammable refrigerants. Only technicians specifically trained in handling flammable refrigerants should service refrigeration equipment containing this refrigerant.
Technicians should gain an understanding of minimizing the risk of fire and the steps to use flammable refrigerants safely.
Room occupants should evacuate the space immediately following the accidental release of this refrigerant.
Personnel commissioning, maintaining, repairing, decommissioning and disposing of appliances with this refrigerant should obtain training and follow practices consistent with Annex HH of UL 60335240, 3rd edition.1 2 3
CAA section 608c2 prohibits knowingly venting or otherwise knowingly releasing or disposing of substitute refrigerants in the course of maintaining, servicing, repairing or disposing of an appliance or industrial process refrigeration.
Department of Transportation requirements for transport of flammable gases must be followed.
Flammable refrigerants being recovered or otherwise disposed of from residential and light commercial air conditioning appliances are likely to be hazardous waste under the Resource Conservation and Recovery Act RCRA see 40 CFR parts 260270.

E:FRFM06MYR2.SGM

06MYR2

Riguardo a questa edizione

Federal Register - May 6, 2021

TitoloFederal Register

PaeseStati Uniti

Data06/05/2021

Conteggio pagine186

Numero di edizioni7798

Prima edizione14/03/1936

Ultima edizione18/06/2026

Scarica questa edizione

Altre edizioni

<<<Mayo 2021>>>
DLMMJVS
1
2345678
9101112131415
16171819202122
23242526272829
3031