Versión en texto ¿Qué es?Dateas es un sitio independiente no afiliado a entidades gubernamentales. La fuente de los documentos PDF aquí publicados es la entidad gubernamental indicada en cada uno de ellos. Las versiones en texto son transcripciones no oficiales que realizamos para facilitar el acceso y la búsqueda de información, pero pueden contener errores o no estar completas.
Fuente: Federal Register
47638
Federal Register / Vol. 86, No. 163 / Thursday, August 26, 2021 / Notices
airflow take precedence over airflow values specified in manufacturer installation instructions or product literature.
In Appendix C to Subpart R, revise section 3.3.7 which specifies modifications to AHRI 12502009 to read:
3.3.7. For unit coolers tested alone, calculate AWEF on the basis that walkin box load is equal to half of the system net capacity, without variation according to high and low load periods, and with EER set according to tested evaporator capacity, as follows:
For Unit Coolers Tested Alone:
The net capacity, qmix,evap, is determined from the test data for the unit cooler at the 38 F suction dewpoint.
BILLING CODE 671701P
BL= 0.5 XCJ.mix,evap
CJ.mix,evap+ 3.412 X EFcomp,on , Emix,rack=
EER
+ EF comp,on Where:
if CJ.mix,evap<10,000 Btu/h if 10,000qmix,evap <20,000 Btu/h if 20,000 CJ.mix,evap<36,000 Btu/h
11
EER= 0.0007qmix,evap+4
18
LF=
BL+ 3 .412 XEF comp,off .
Clmix,evap+ 3.412XEFcomp,off
BL
AWEF=.
.
Emix,rack XLF + EF comp,offX 1-LF
BL is the non-equipment-related box load LF is the load factor And other symbols are as defined in Section 8 of ARRI 12502009.
jbell on DSKJLSW7X2PROD with NOTICES
BILLING CODE 671701C
3 Representations. LRC Coil may not make representations about the efficiency of a basic model listed in paragraph 1 for compliance, marketing, or other purposes unless that basic model has been tested in accordance with the provisions set forth in this alternate test procedure and such representations fairly disclose the results of such testing.
4 This Interim Waiver Order shall remain in effect according to the provisions of 10 CFR 431.401.
5 This Interim Waiver Order is issued on the condition that the statements and representations provided by LRC Coil are valid. If LRC Coil makes any modifications to the controls or configurations of a basic model subject to this Interim Waiver Order, such
VerDate Sep<11>2014
17:30 Aug 25, 2021
Jkt 253001
modifications will render the waiver invalid with respect to that basic model, and LRC Coil will either be required to use the current Federal test method or submit a new application for a test procedure waiver. DOE may rescind or modify this waiver at any time if it determines the factual basis underlying the petition for the Interim Waiver Order is incorrect, or the results from the alternate test procedure are unrepresentative of a basic models true energy consumption characteristics. 10
CFR 431.401k1. Likewise, LRC Coil may request that DOE rescind or modify the Interim Waiver Order if LRC Coil discovers an error in the information provided to DOE as part of its petition, determines that the interim waiver is no longer needed, or for other appropriate reasons. 10 CFR 431.401k2.
PO 00000
Frm 00025
Fmt 4703
Sfmt 4703
6 Issuance of this Interim Waiver Order does not release LRC Coil from the applicable requirements set forth at 10 CFR part 429.
DOE makes decisions on waivers and interim waivers for only those basic models specifically set out in the petition, not future models that may be manufactured by the petitioner. LRC
Coil may submit a new or amended petition for waiver and request for grant of interim waiver, as appropriate, for additional basic models of Walk-in Cooler Refrigeration Systems.
Alternatively, if appropriate, LRC Coil may request that DOE extend the scope of a waiver or an interim waiver to include additional basic models employing the same technology as the basic models set forth in the original