Versión en texto ¿Qué es?Dateas es un sitio independiente no afiliado a entidades gubernamentales. La fuente de los documentos PDF aquí publicados es la entidad gubernamental indicada en cada uno de ellos. Las versiones en texto son transcripciones no oficiales que realizamos para facilitar el acceso y la búsqueda de información, pero pueden contener errores o no estar completas.

Fuente: Federal Register

Federal Register / Vol. 86, No. 58 / Monday, March 29, 2021 / Rules and Regulations
16453

BILLING CODE 351033P

l

10.0%

1---------------------"------

0.0%

1------+-----+------1----+-----+------c ia
:i

E

.g a::
w w .5

50%

ffli-10.0%
c
60%

70%

1--------------= -.a =--------

l!
u
-+- Single-Speed Room AC
-30.0% __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
Cooling Load % of Unit Cooling Capacity
Figure 111-1 Change in EER for Reduced Cooling Loads at 95 F Outdoor Dry-Bulb Temperature, Unit 1
30.0%

-

20.0%

-0

111

.9

:i
10.0%

u.

E

.g
0.0%
50%

0::

LI.I
LI.I

60%

70%

-10.0%

:0
C:
111

6

-20.0% 1--=-=------------1-=:a =w,,an-Room:1C

-e-Single-Speed Room AC
-30.0%

Cooling Load % of Unit Cooling Capacity
In Figures III1 and III2, the distance of each data point from the x-axis represents the change in efficiency relative to the full-load efficiency for each unit at the outdoor test condition used.12 The single-speed room AC
efficiency decreases in correlation with a reduction in cooling load, reflecting
VerDate Sep<11>2014

17:42 Mar 26, 2021

Jkt 253001

cycling losses that become relatively larger as the cooling load decreases. In contrast, the efficiency of the variablespeed room AC increases as the cooling load decreases, reflecting the lack of cycling losses and inherent improvements in system efficiency associated with lower-capacity
PO 00000

Frm 00009

Fmt 4701

Sfmt 4700

operation. As explained in the June 2020 NOPR, these results demonstrate that the previous test procedure does not account for significant efficiency gains that variable-speed room ACs can achieve under reduced temperature conditions. 85 FR 35700, 35708 Jun. 11, 2020.

E:FRFM29MRR2.SGM

29MRR2

ER29MR21.000

BILLING CODE 351033C

ER29MR21.001

Figure 111-2 Change in EER for Reduced Cooling Loads at 82 F Outdoor Dry-Bulb Temperature, Unit 2

Acerca de esta edición

Federal Register - March 29, 2021

TítuloFederal Register

PaísEstados Unidos de América

Fecha29/03/2021

Nro. de páginas235

Nro. de ediciones7801

Primera edición14/03/1936

Ultima edición24/06/2026

Descargar esta edición

Otras ediciones

<<<Marzo 2021>>>
DLMMJVS
123456
78910111213
14151617181920
21222324252627
28293031