Federal Register - February 23, 2021
Versión en texto ¿Qué es?Dateas es un sitio independiente no afiliado a entidades gubernamentales. La fuente de los documentos PDF aquí publicados es la entidad gubernamental indicada en cada uno de ellos. Las versiones en texto son transcripciones no oficiales que realizamos para facilitar el acceso y la búsqueda de información, pero pueden contener errores o no estar completas.
Fuente: Federal Register
11018
Federal Register / Vol. 86, No. 34 / Tuesday, February 23, 2021 / Notices LICENSE AMENDMENT ISSUANCESContinued
Tennessee Valley Authority; Sequoyah Nuclear Plant, Units 1 and 2; Hamilton County, TN; Tennessee Valley Authority; Watts Bar Nuclear Plant, Units 1 and 2; Rhea County, TN
Docket Nos
Amendment Date
ADAMS Accession No
Amendment Nos
Brief Description of Amendments
Public Comments Received as to Proposed NSHC Yes/No.
50327, 50328, 50390, 50391.
January 25, 2021.
ML20350B493.
Sequoyah352 Unit 1, 346 Unit 2; Watts Bar141 Unit 1, and 47 Unit 2.
The amendments revised the technical specifications to adopt Technical Specifications Task Force TSTF Traveler TSTF569, Revision 2, Revise Response Time Testing Definition ADAMS Accession No. ML19176A034.
No.
Vistra Operations Company LLC; Comanche Peak Nuclear Power Plant, Unit Nos. 1 and 2; Somervell County, TX
Docket Nos
Amendment Date
ADAMS Accession No
Amendment Nos
Brief Description of Amendments
Public Comments Received as to Proposed NSHC Yes/No.
IV. Previously Published Notices of Consideration of Issuance of Amendments to Facility Operating Licenses and Combined Licenses, Proposed No Significant Hazards Consideration Determination, and Opportunity for a Hearing The following notices were previously published as separate individual
50445, 50446.
February 1, 2021.
ML20346A019.
177 Unit 1 and 177 Unit 2.
The amendments revised Technical Specification TS 3.8.1, AC Alternating Current SourcesOperating, to change the emergency diesel generator surveillance requirement SR steady-state frequency band in multiple SRs from a band from 58.8 hertz Hz to 61.2
Hz to a band from 59.9 Hz to 60.1 Hz. The amendments also removed historical information from TS 3.8.1 and a Note from SR 3.8.1.13.
No.
notices. They were published as individual notices either because time did not allow the Commission to wait for this monthly notice or because the action involved exigent circumstances.
They are repeated here because the monthly notice lists all amendments issued or proposed to be issued involving NSHC.
For details, including the applicable notice period, see the individual notice in the Federal Register on the day and page cited.
LICENSE AMENDMENT REQUESTSREPEAT OF INDIVIDUAL FEDERAL REGISTER NOTICE
Indiana Michigan Power Company; Donald C. Cook Nuclear Plant, Unit 2; Berrien County, MI
Docket Nos
Application Date
ADAMS Accession No
Brief Description of Amendments
Date & Cite of Federal Register Individual Notice.
Expiration Dates for Public Comments & Hearing Requests.
50316.
December 14, 2020.
ML20363A011.
The proposed amendment would revise the Donald C. Cook Nuclear Plant, Unit 2, technical specifications to allow a one-time change to permit the current integrated leak rate test interval of 15 years to be extended by approximately 18 months to no later than the plant startup after the fall 2022 refueling outage.
January 12, 2021 86 FR 2460.
February 11, 2021 Public Comments; March 15, 2021 Hearing Requests.
Tennessee Valley Authority; Watts Bar Nuclear Plant, Unit 2; Rhea County, TN
Docket Nos
Application Date
ADAMS Accession No
Brief Description of Amendments
Date & Cite of Federal Register Individual Notice.
Expiration Dates for Public Comments & Hearing Requests.
VerDate Sep<11>2014
18:36 Feb 22, 2021
Jkt 253001
50391.
December 23, 2020.
ML20358A141.
The proposed amendment would revise the Watts Bar Updated Final Safety Analysis Report to apply alternate eddy current probabilities of detection to indications of axial outer diameter stress corrosion cracking at tube support plates in the Watts Bar, Unit 2, steam generators for the beginning-of-cycle voltage distribution in support of the Watts Bar, Unit 2, operational assessment. The proposed probability of determination values will only be used until the Watts Bar, Unit 2, steam generators are replaced.
January 8, 2021 86 FR 1545.
February 8, 2021 Public Comments; March 9, 2021 Hearing Requests.
PO 00000
Frm 00100
Fmt 4703
Sfmt 4703
E:FRFM23FEN1.SGM
23FEN1